Skip to content

Limit and control profiles

2.6 Limit and control profiles

Profiles are time-varying values. A profile can be attached to an analogue or counter limit to cause that limit to vary across a week. They can also be attached to a control profile object.

2.6.1 Limit profiles

A Limit Profile can be attached to an analogue or counter alarm limit or be attached and used by a control profile.

The information in Table 18 is used to define limit profiles within the object: limitProfile.

Information Type JSON Name Mandatory Description
Limit Profile Index Integer num Yes An index for this limit.
Values Array of Numbers values Yes Values array - first value applies at first time.
Times Array of Integer times Yes Times array - in milliseconds from start of day.
Type Integer type No Whether the profile is stepped (0) or linear (1). Stepped is \'step first\'. Stepped is the default.
Interpolate Integer inter No The interpolation time (in milliseconds) is the time period used to compute a new value for the profile, interpolating between two profile points. If set to 0 then no interpolation is performed. Applies to control values.

Table 18: Information used in defining limit profiles for analogue and counter points

2.6.2 Control profiles

The information in Table 19 is used to define limit profiles within the object: controlProfile.

Information Type JSON Name Mandatory Description
Parent Point Integer parent Yes Analogue or binary output point number.
Parent Type String parentType Yes "ao" or "bo"
Control Profile Index Integer num Yes Control Profile Index for this profile.
Limit Name String name No A human readable name for the limit.
Monday Profile Integer mon No Profile number for Monday.
Tuesday Profile Integer tue No Profile number for Tuesday.
Wednesday Profile Integer wed No Profile number for Wednesday.
Thursday Profile Integer thu No Profile number for Thursday.
Friday Profile Integer fri No Profile number for Friday.
Saturday Profile Integer sat No Profile number for Saturday.
Sunday Profile Integer sun No Profile number for Sunday.

Table 19: Information used in defining a control profile

The Interpolate field in the Limit Profile determines how often a value is set on the control output.