3 Controls and overrides

This section provides information on the controls and overrides used in the protocol.

3.1 Controls

NOTE: Applies to analogue output, binary output, and string points only.

If supported as listed in the features section of the profile, the SA may send a message to the FD to control a point output. The evidence of an output can be received through the value received in the data message, as configured on the output point.

[UUID]/DOWN/control

The QoS is 2, and the message is:

  • Control by point identifications:
{
    "c":[{"ao":1,"v":1}]
}
  • Or by name:
{
    "c":[{"name":"Pump 1.Command","v":1}]
}
  • If the value is a string:
{
    "c":[{"name":"Pump 1.State","vs":"Fail"}]
}

Use the value property "v" only for numeric point types (Analog and Binary) and "vs" only for the string point type.

If this is a pulsed control, that is, the 1 bit binary output has a non-zero pulse duration, the value is the time in milliseconds which overrides the value specified in its configuration.

If a point attached to the "Internal" Device Link is to be modified by controls, then it must be typed as an analogue output or binary output.

3.2 Overriding a point

Subject to the canOverride property of points.

Extensions cannot be overridden.

When overridden the point quality is set accordingly.

If supported as listed in the features section of the profile, the SA may send a message to the FD to override the value of an input point.

[UUID]/DOWN/override

The QoS is 2, and the messages are:

  • Override by point identifications:
{
    "o":[{"ai":1,"v":1}]
}
  • Or by name:
{
    "o":[{"name":"Pump 1.Rate","v":1}]
}
  • If the value is a string:
{
    "o":[{"ai":1,"vs":"test value"}]
}
  • Release by point identifications:
{
    "r":[{"ai":1}]
}
  • Or by name:
{
    "r":[{"name":"Pump 1.Rate"}]
}

Use the value property \"v\" only for numeric point types (Analog, Counter and Binary) and \"vs\" only for the string point type.